WRF Hot Air Furnace for Tobacco Redrying Plants

November 13,2026    hxboiler    

A tobacco redrying plant is one of the most sensitive environments in any heat using industry. Strip leaf arrives at the primary processing line with the aromas that buyers pay for, and every kilogram of that leaf passes through a dryer where hot air touches it directly. If the air carries combustion products, the leaf adsorbs the odour and the style of the cured tobacco changes in a way that grading and blending cannot undo. That single fact decides the heat supply: a redrying plant needs an indirect hot air furnace, one where the flame and the flue gas stay on their own side of a heat exchanger while clean process air is heated on the other. This article maps the heat users of a tobacco primary processing plant, sets out the temperature windows that curing and redrying actually run at, and works a complete sizing example on the WRF-Y(Q) series oil and gas fired hot air furnace range.

The scope is a single line redrying plant processing strip leaf at about 12,000 kg per hour on a two shift pattern. The figures below are realistic planning estimates drawn from tobacco processing practice; every project should confirm them against the actual line layout, leaf moisture schedule and local climate before a furnace is ordered.

Why Indirect Hot Air Is the Only Acceptable Choice for Leaf

Cured tobacco is hygroscopic and aromatic. Volatile compounds on the leaf surface equilibrate with whatever the surrounding air carries, so combustion odour, oil mist and flue gas acids all end up in the product. Direct fired heaters, the kind used freely for stone and aggregate drying, are excluded from leaf contact duty for this reason, and most tobacco quality standards treat taint from flue gas as a defect rather than a process variation. Indirect heating separates the streams: fuel burns in a combustion chamber, the flue gas sweeps through the hot side of a plate heat exchanger and out to stack, while process air passes through the cold side, is filtered and enters the dryer zones carrying nothing but heat.

The second requirement is temperature accuracy. Redrying schedules hold zone inlet air within a few kelvin of a set point, because colour, fill and moisture after the dryer all follow the zone curve. A furnace that drifts, or one that overshoots during load steps, costs quality that no later step recovers. The third requirement is continuity: a dryer trip in the middle of a production day leaves leaf standing in a warm, humid zone, and the schedule loses more than the furnace does. These three requirements, cleanliness, accuracy and availability, shape every selection decision below.

The Heat User Map of a Tobacco Redrying Plant

The table below lists the heat users of a typical single line plant. The dryer zones dominate the connected load, but the conditioning and workshop users set the floor load that the furnace must hold overnight and between batches.

Heat userAir or medium temperatureLoad characterConsequence of a shortfall
Redrying dryer zone 1, high moisture sectionAir at 90 to 100 degrees CelsiusContinuous during productionMoisture stays high, dryer throughput drops
Redrying dryer zone 2, main drying sectionAir at 100 to 120 degrees CelsiusContinuous, largest single userFinal moisture above 12 percent, packing risk
Redrying dryer zone 3, cooling and conditioning sectionAir at 45 to 60 degrees CelsiusContinuous, moderatePoor fill, unstable moisture before casing
Conditioning cylinders before threshingAir at 50 to 60 degrees CelsiusBatch, follows line startUneven lamina separation, high broken leaf loss
Workshop air handling make up airAir at 30 to 45 degrees Celsius in winterShift based, climate dependentCold draughts, condensation on halls and ducts
Packing hall dehumidification regenerationAir at 60 to 80 degrees CelsiusContinuous in humid seasonsCartons and film pick up moisture, casing softens
Hot water for washdown and staff55 to 70 degrees CelsiusShift basedSanitation quality only

Two observations follow. The connected load is dominated by one or two dryer sections that run at 100 to 120 degrees Celsius, which is a moderate temperature band that an indirect plate heat exchanger furnace reaches comfortably and holds without stress. And the floor load, the conditioning cylinders and workshop air that run before and after the dryer, is roughly a fifth of the peak, so the furnace needs a clean turn down rather than an on and off profile.

Temperature Windows Across Curing and Redrying

Tobacco processing runs a ladder of low and moderate air temperatures from the farm to the packed case. The table below collects the windows in one place, because a furnace supplier who sees the full ladder can propose one machine that serves the whole plant instead of a special unit for each zone.

Process stepAir temperature windowNotes for the heat supply
Flue curing on the farm, yellowing phase35 to 38 degrees CelsiusSmall barn burners, outside the scope of a plant furnace
Flue curing on the farm, colour fixing38 to 54 degrees CelsiusFan driven, close control, again farm scale
Flue curing on the farm, stem drying54 to 68 degrees CelsiusRamp rate limited, not load limited
Leaf conditioning cylinders50 to 60 degrees CelsiusSteam or hot air coils, batch duty
Redrying dryer, wet end90 to 100 degrees CelsiusHighest humidity, air must stay above dew point in the zone
Redrying dryer, main drying100 to 120 degrees CelsiusPeak connected load of the plant
Redrying dryer, cooling section45 to 60 degrees CelsiusAmbient air with limited trim heat
Casing and flavour application air50 to 70 degrees CelsiusGentle air, uniformity matters more than temperature

The whole plant ladder ends below 120 degrees Celsius of air, which is why the published outlet band of the furnace, up to 400 degrees Celsius at the top of its range, gives the plant more headroom than it needs. Headroom is worth having: it lets the same furnace serve an added stem drying line or an expanded pack hall later, and it keeps the burner in its efficient mid band instead of at maximum all day.

Direct or Indirect: What Changes When the Flame Stays Sealed

The comparison below sets a direct gas burner against an indirect plate heat exchanger furnace on the duties a redrying plant actually asks for.

AspectDirect gas burner in the air streamIndirect WRF-Y(Q) furnace
Contact of combustion products with leafFull contact, moisture of combustion enters the dryerNone, flue gas leaves through its own stack
Odour and taint risk on the leafPresent, harder to grade and blend awayEliminated by the separating wall of the exchanger
Air humidity control in the zoneBurner adds water vapour with every unit of fuelProcess air humidity depends only on the recirculation and vent schedule
Temperature stability across load stepsFast but coupled to combustion noise and pulsationPlate exchanger smooths the transfer, modulating burner holds within 2 to 3 K
Fuel flexibilityGas only in most layoutsNatural gas or light oil on the published design fuel list
Efficiency at partial loadGood, but stack loss follows the excess airWaste heat recovery option holds efficiency and saves 5 to 8 percent fuel
Maintenance exposureBurner inside ductwork, access awkwardUnitised furnace cell, burner, fan and filter all reachable from the floor

The honest summary is that direct firing is cheaper to buy and unacceptable to use on leaf. Every tobacco primary plant therefore builds on indirect heat, and the questions that remain are sizing, control and fuel.

Inside the WRF-Y(Q) Series

The WRF-Y(Q) series is a unitised indirect hot air furnace. Fuel burns in a combustion chamber built around a heat resistant stainless steel core, the flue gas makes multiple passes through a plate heat exchanger, and process air is drawn through an air filter, heated on the clean side and delivered by the fan to the plant ducting. Nothing separates the flame from the air except the exchanger wall, and nothing but heat crosses it.

Three circuit cross flow plate heat exchanger

The exchanger arranges air and flue gas in a three circuit cross flow, which keeps the temperature difference along each wall high and the wall temperature itself moderate. The published description credits this layout with high heat exchange efficiency in a compact volume, and the practical benefit for a tobacco plant is steadier zone air: the exchanger does not chase the burner, so zone set points hold within a few kelvin while the load moves between sections.

Waste heat recovery option

Units fitted with the waste heat recovery device preheat incoming combustion air with the stack gas, which lifts the overall heat exchange efficiency above 90 percent and saves 5 to 8 percent of fuel against the base configuration. On a plant that runs two shifts and a half year long season, that saving pays for the option inside a few seasons, and the lower stack temperature also simplifies duct and fan selection behind the furnace.

SUS304 core and 150 mm insulation

The furnace core is heat resistant SUS304 stainless steel, welded inside a double layer steel skeleton, and the insulation layer is 150 mm thick. The insulation matters more than it looks in a tobacco plant: the furnace house is usually close to the processing hall, and a cool shell keeps the work area usable and the filtration air drawn from the house clean.

Automatic control and the shutdown purge

The control system modulates the burner across a furnace temperature range of 60 to 220 degrees Celsius with automatic high and low fire switching, and after shutdown the fan continues to run for 15 minutes to purge residual heat. The purge protects the exchanger and, just as important for the process, stops the last metres of ducting from baking any leaf that stands in the dryer when the line stops.

The ZRFQ Model Range and Published Parameters

The range is published under the ZRFQ designation, rated in units of 10 thousand kilocalories per hour, one of which equals 11.63 kW. The table below reproduces the published parameters of the fifteen models. Rated heat power spans 60 to 4200 units of 10 thousand kilocalories per hour, roughly 0.07 to 4.88 MW, with outlet air at 100 to 400 degrees Celsius, atmospheric working pressure, and natural gas or light oil as design fuels. The furnace listed at the product page headline reaches 0.6 to 2.4 MW with a test thermal efficiency of at least 98 percent on the bench.

ModelRated heat power (10^4 kcal/h)Approximate MWOutlet air (C)EfficiencyFuel consumption, natural gas (Nm3/h)Fuel consumption, light oil (kg/h)Transport size L x W x H (m)
ZRFQ-5-YQ600.07100 to 400at least 98 percent3.5 to 11.57 to 141.5 x 0.6 x 0.8
ZRFQ-10-YQ1200.14100 to 400at least 98 percent10 to 2813 to 262.6 x 0.9 x 1.2
ZRFQ-20-YQ2400.28100 to 400at least 98 percent8 to 4115 to 332.7 x 1.0 x 1.3
ZRFQ-30-YQ3500.41100 to 400at least 98 percent8 to 4115 to 332.5 x 1.1 x 1.45
ZRFQ-40-YQ5000.58100 to 400at least 98 percent8 to 4115 to 333.5 x 1.2 x 1.55
ZRFQ-60-YQ7000.81100 to 400at least 98 percent20 to 8520 to 753.5 x 1.3 x 1.65
ZRFQ-80-YQ10501.22100 to 400at least 98 percent30 to 12030 to 904.0 x 1.4 x 1.75
ZRFQ-100-YQ12001.40100 to 400at least 98 percent5 to 15035 to 1104.0 x 1.5 x 1.85
ZRFQ-120-YQ14001.63100 to 400at least 98 percent50 to 21067.5 to 1774.0 x 1.7 x 2.05
ZRFQ-150-YQ17502.03100 to 400at least 98 percent50 to 26080 to 2204.9 x 1.8 x 2.2
ZRFQ-200-YQ24002.79100 to 400at least 98 percent90 to 320100 to 2905.2 x 1.9 x 2.3
ZRFQ-240-YQ28003.26100 to 400at least 98 percent50 to 36080 to 3295.6 x 2.0 x 2.4
ZRFQ-300-YQ36004.19100 to 400at least 98 percent100 to 450120 to 3605.6 x 2.05 x 2.5
ZRFQ-360-YQ42004.88100 to 400at least 98 percent100 to 450120 to 3605.6 x 2.1 x 2.6
ZRFQ-400-YQ42004.88100 to 400at least 98 percent100 to 450120 to 3606.0 x 2.1 x 2.6

The published application list of the series names food processing, automotive paint drying, breeding farms, chemical, building materials and paper industries among its users, and the application pages collect reference installations by industry. Tobacco primary processing sits naturally in the same family, because the duty, clean filtered air at a moderate and precisely held temperature, is exactly what the series is built around.

A Four Step Sizing Method with a Worked Example

Size the furnace from the dryer heat balance, not from the dryer nameplate. The four steps below take the worked example plant from connected load to a model choice.

Step one: the evaporation load of the dryer zones

Strip leaf enters the redrying dryer at about 22 percent moisture and leaves the drying sections at about 12 percent before conditioning and cooling. At 12,000 kg per hour of leaf, the water evaporated per hour is 12,000 multiplied by 10 divided by 88, which is about 1,364 kg of water. Redrying practice, with the fan and vent load included, costs roughly 3,200 kJ per kilogram of water at this temperature band, so the dryer zones demand about 1,364 multiplied by 3,200 divided by 3,600, or 1,212 kW of delivered heat.

Step two: add the remaining users at their real diversity

The conditioning cylinders take 150 kW, the casing air 180 kW, winter make up air for the halls 250 kW, dehumidification regeneration 90 kW and hot water 60 kW. The connected total is 1,212 plus 150 plus 180 plus 250 plus 90 plus 60, which is 1,942 kW.

Step three: apply simultaneity and a growth margin

Not every user peaks at once: the make up air load tracks winter while the dryer runs its production schedule, so a simultaneity factor of 0.85 is realistic for a two shift plant. The design load is 1,942 multiplied by 0.85, or 1,651 kW, and with a 10 percent margin for an added pack hall or stem line it becomes 1,816 kW.

Step four: choose the model and check the duty point

OptionRated outputDuty point at 1,816 kWAssessment
ZRFQ-150-YQ1.75 MW104 percentAbove rated output, no margin, rejected
ZRFQ-200-YQ2.40 MW76 percentComfortable mid band, burner modulates cleanly, recommended
ZRFQ-240-YQ2.80 MW65 percentFor a planned second line, higher capital, reserve option

The ZRFQ-200-YQ carries the design load at 76 percent of rating, which keeps the burner in its modulating band through the day and leaves real headroom for the shoulder duties. A plant with a firm second line in its plan should price the ZRFQ-240-YQ instead, and the difference in capital is usually smaller than the cost of splitting the heat supply in two later.

Air Distribution, Filtration and Control

The furnace is one part of the system; the air side decides whether the dryer zones see what the schedule asks for. Draw process air from a clean part of the furnace house, pass it through the filter stage on the furnace inlet, and keep the filter maintenance on a fixed schedule, because a blinded filter starves the fan and shifts the duty point without any alarm. Between the furnace and the dryer zones, use blending dampers at each zone inlet so the zone can mix furnace air with recirculated hall air, which is how a 120 degree drying zone and a 50 degree conditioning zone share one furnace. Instrument each zone with its own inlet sensor and let the zone damper, not the burner, carry the fast corrections; the burner should follow the furnace outlet temperature slowly, which keeps the exchanger thermally steady and the zone curves flat.

Insulate hot ducting with at least 100 mm of mineral wool and check the duct joints on the filter side of the system, because tobacco dust settles on every warm surface and a leaky joint spreads it. The shutdown purge of 15 minutes already protects the exchanger; a similar short run on of the dryer fans after a line stop keeps the zones from stewing the last leaf through them.

Fuel Choice and Consumption per MWh

The series takes natural gas or light oil as design fuels, which covers the two supply situations a redrying plant usually faces: gas where the industrial estate has a pipeline, oil where the plant is remote or the gas connection is unreliable. The table converts delivered heat into fuel at typical efficiencies and prices that should be replaced with local contract figures.

FuelLower heating valueFuel per MWh of delivered heatIndicative priceIndicative fuel cost per MWh
Natural gas35.6 MJ/Nm3108 Nm30.35 USD per Nm338 USD
LPG, where piped gas is absent46.0 MJ/kg85 kg0.65 USD per kg55 USD
Light oil40.8 MJ/kg92 kg0.70 USD per kg64 USD

For the worked example plant, running 6,000 production hours a year at an average 70 percent of the 2.40 MW rating delivers about 10,080 MWh of heat, which is roughly 1.09 million cubic metres of natural gas before the waste heat recovery saving. The recovery device saves 5 to 8 percent of that, or 55,000 to 87,000 cubic metres a year, which at typical industrial gas prices is a substantial annual line item for one optional assembly.

Installation and Commissioning Checklist

ItemWhat to confirm
Furnace house locationUpwind of leaf intake, clean air for the filter stage, service access on the burner and fan sides
Gas or oil trainPressure and pipe size per the model data, double block and bleed on the gas train, oil pump and nozzle heater on light oil
StackHeight and termination per local rules, condensate drain if the recovery device is fitted
Ducting and dampersZone blending dampers with actuators, insulation complete, test points at each zone inlet
Filter stagePanel or bag filters on the process air inlet, differential pressure gauge with an alarm point
Controls interfaceFurnace outlet control wired to the dryer zone schedule, remote start and stop from the line control room, alarm relay to the plant historian
SafetyFlame detection, purge interlock before ignition, high temperature cut out, emergency stop at the furnace and at the line

A commissioning day that ends with each zone inlet verified against its schedule set point, the purge sequence demonstrated, and the filter alarm tested, is a commissioning day that prevents the three most common first season problems: drifting zones, a furnace that trips on start and a filter that blinds silently.

Maintenance Calendar Through the Season

IntervalTask
DailyLog furnace outlet temperature, zone inlet temperatures, filter differential pressure, burner modulation and stack temperature
WeeklyCheck flame signal strength, inspect the filter stage, listen to the fan bearings, test the interlocks
MonthlyClean the filter stage as indicated by the gauge, inspect duct insulation and damper travel, verify the shutdown purge duration
QuarterlyService the burner, check the gas or oil train valves, clean the fan wheel, inspect the exchanger access panels for dust build up
Annually, before the seasonFull burner overhaul, exchanger internal inspection, repack gland seals, recalibrate zone sensors and the outlet controller

Tobacco adds one habit to a normal hot air furnace calendar: housekeeping for leaf dust. The filter stage, the furnace house floor and the duct surfaces near the dampers collect dust that is both a hygiene and a combustible concern, and a cleaning routine tied to the daily log keeps both risks small.

Five Mistakes Plants Make with Hot Air Furnaces

First, sizing from the dryer motor instead of the heat balance: the fan ratings describe air movement, not heat, and the evaporation calculation above is the only sound starting point. Second, letting the furnace outlet carry the fast control: zones that chase the burner oscillate, and the fix is always zone dampers with a slow burner. Third, ignoring the filter stage until zones drift, then blaming the furnace, when the real fault is a blinded filter that starves the fan. Fourth, buying without the waste heat recovery option on a long season plant, which leaves 5 to 8 percent of the fuel bill on the stack every year. Fifth, locating the furnace house where the filter stage draws dusty or tainted air, because no exchanger cleans the air, it only heats it, and the cleanliness of the output air is decided at the inlet.

Supplier Qualifications, OEM and Custom Development

A heat supply that every kilogram of leaf depends on deserves a supplier with more than a catalogue. Henan Hengxin Boiler Co., Ltd. manufactures under a special equipment production licence and holds ISO9001 and ISO14001 certification with 3A enterprise credit standing, and the certificates page lists the documents for review. The company builds oil and gas fired hot air furnaces alongside its boiler ranges, supports drawings from the customer for custom development, and offers OEM supply for partners who assemble complete processing lines. Where a plant prefers a solid fuel site, the companion biomass (coal) hot blast stove range serves the same indirect hot air duty on agricultural fuel, and the YGL biomass thermal fluid heater covers the high temperature coils elsewhere on the site.

FAQ: Questions Tobacco Plant Engineers Ask

Can one furnace serve the dryer zones and the workshop air handlers at the same time?

Yes. The furnace delivers one stream of hot air at its outlet, and each user takes its share through a blending damper that mixes furnace air with recirculated air down to the temperature that user needs. A 120 degree drying zone and a 45 degree make up air coil are two settings of the same damper logic, and the burner follows the aggregate demand with slow modulation.

How clean is the output air, and what proves it?

The process air never touches combustion products: the plate exchanger wall separates the streams, and the flue gas leaves through its own stack. In practice the output air is the intake air plus heat, filtered at the inlet. Plants that need documentary proof run odour panel tests or gas analysis on the output side after commissioning, and a simple smoke pencil around the exchanger access panels during operation confirms the separation.

What happens if the burner trips in the middle of a drying run?

The zones coast on their thermal inertia and the dryer fans keep running, so the leaf sees a falling temperature rather than a dead zone. The furnace restarts on its purge and ignition sequence, which takes a few minutes, and the zone dampers close toward recirculation during the gap to hold what heat the ducts carry. A line that cannot tolerate the gap at all keeps a second smaller furnace on the same header, which is a layout the factory supports.

What information does the factory need to quote?

The leaf throughput and moisture schedule across the dryer zones, the zone temperature set points and how many run at once, the make up air and dehumidification duties, the fuel available and its pressure or grade, and the dimensions of the furnace house. With those figures the factory returns a model selection, an air side layout with filter and damper staging, an estimated fuel consumption and a delivery schedule.

Start with the Zone Heat Balance

A redrying plant that holds its zone curves through the season is a plant whose heat supply was sized from the evaporation balance, filtered at the inlet, and controlled at the zone dampers rather than at the burner. The WRF-Y(Q) series covers that duty from 0.6 to 2.4 MW in its headline band and beyond across the full fifteen model range, on natural gas or light oil, with an indirect plate exchanger between the flame and the leaf. Henan Hengxin Boiler Co., Ltd. supports the sizing with application engineers who have furnished hot air for food, drying and surface treatment plants, and the company welcomes drawings and process data for custom development. Send the zone schedule and the fuel available, and a selection with layout and consumption figures follows for review before any commitment is made.

RECOMMENDED PRODUCTS

  • 1Rated Heat Power(MW)120-600
  • 2Rated Working Pressure(MPa)1.0
  • 3Max Working Temperature(℃))320
  • 4Design FuelBiomass Fuel
  • 1Rated Steam Capacity(t/h)6-150
  • 2Rated Working Pressure(MPa)1.25-2.5
  • 3Saturated Steam Temperature(℃))194-225
  • 4Design FuelNatural Gas,Light Oil,Heavy Oil etc.
  • 1Rated Power(kw)350-14000
  • 2Adjust WayFully outomatic regulation with two-stages fire
  • 3Combustion WayMicro-positive pressure chamber combustion
  • 4Design FuelNatural Gas,Light Oil,Heavy Oil etc.
  • 1Rated Heat Power(MW)0.35-7
  • 2Rated Working Pressure(MPa)1.0
  • 3Rated Outlet/Return Temperature(℃))115/70
  • 4Design FuelCoal Biomass Fuel
  • 1Rated Steam Capacity(t/h)0.5-6
  • 2Rated Working Pressure(MPa)1.25
  • 3Saturated Steam Temperature(℃))194
  • 4Design FuelCoal Biomass Fuel
  • 1Rated calorific value(Kcal)120-2350
  • 2Working mediumAir
  • 3Rated Outlet/Return Temperature(℃))50-220
  • 4Design Fuel3850kcal/kg

Inquiry

Contact

Hengxin
Taikang Hengxin Boiler Co., Ltd. is located in Taikang County, Zhoukou City, Henan Province, the company was founded in 2016, is a specialized in boiler,pressure vessel products research and development, design, production, sales, installation, transformation and aseries of services. 7 years of development, Hengxin boiler has established a complete product line.The product line includes 8 kinds of oil and gas boiler, coal boiler, biomass boiler, hot blast stove, heat conductionoilboiler,electric boiler,waste heat boiler, circulating fluidized bed boiler,pressure vessel,28productseries,morethan 300models.Products cover agriculture,forestry,husbandryand fishery, food, textile, manufacturing, chemical, building materials, metallurgy and minerals, power supply and heating and many other industries. Hengxin Boiler,asone of the earliestenter prisesengaged in the boiler industry in China,was the first toobtain the B-classboiler manufacturing license issuedby the General Administration of Qua...